Dettagli:
Contatto
Ora chiacchieri
|
| Condizione: | Nuovo di zecca originale | Garanzia: | un anno |
|---|---|---|---|
| Applicazione: | industria chimica del gasolio | Modo di spedizione: | DHL Fedex |
The MTL7767+ is a high-performance 2-channel shunt-diode safety barrier (Zener barrier) from Eaton's Crouse-Hinds series MTL7700 range, specifically engineered for positive DC systems up to 12V DC requiring intrinsic safety protection in hazardous areas.
This passive device limits the voltage and current that can reach a hazardous area under fault conditions, preventing ignition of flammable atmospheres. With a safety description of 15V, 100 Ω, 150mA, the MTL7767+ is the ideal solution for protecting low-level DC circuits in Zone 0, 1, and 2 hazardous locations (gas groups IIC, IIB, IIA).
| Code Segment | Meaning |
|---|---|
| MTL | MTL Instruments Group (now Eaton) |
| 77 | MTL7700 series — Shunt-diode safety barriers |
| 67 | Specific barrier configuration for low-level positive DC systems |
| + | Positive polarity configuration |
| Parameter | Value |
|---|---|
| Manufacturer | Eaton (Crouse-Hinds series MTL) |
| Series | MTL7700 Range |
| Product Model | MTL7767+ |
| Product Type | Shunt-Diode Safety Barrier (Zener Barrier) |
| Number of Channels | 2 (dual-channel) |
| Polarity | Positive (+) |
| Parameter | Value |
|---|---|
| Safety Description | 15V, 100Ω, 150mA |
| Working Voltage (Vwkg) | 12V DC nominal (low-level DC systems) |
| End-to-End Resistance | 110Ω Min to 119Ω Max |
| Maximum Current | 150mA |
| Parameter | Value |
|---|---|
| Gas Groups | IIC, IIB, IIA |
| Zones | Zone 0, 1, 2 |
| Equipment Protection Level (EPL) | Ga, Gb, Gc |
| Certification | ATEX II (1) GD [Ex ia] IIC |
| Parameter | Value |
|---|---|
| Width | 12 mm |
| Height | 85 mm / 90 mm |
| Depth | 105 mm |
| Weight | 0.120 kg / 120 g |
| Enclosure Material | Polycarbonate |
| Mounting | DIN rail (35 mm T-section) |
| Terminals | Removable screw terminals |
The MTL7767+ is a passive shunt-diode safety barrier that operates on the Zener barrier principle. It limits both voltage and current that can be delivered to a hazardous area circuit under fault conditions.
The MTL7767+ is specifically designed for positive DC system protection in hazardous area installations:
| Industry | Application |
|---|---|
| Oil & Gas | Low-level DC logic circuits and sensor inputs on offshore platforms and refineries |
| Chemical Processing | 12V DC control circuits, digital input protection in explosive atmospheres |
| Pharmaceutical | Low-voltage DC systems for batch processing equipment requiring Ex protection |
| Factory Automation | 12V DC proximity sensors, limit switches, and digital I/O protection |
| Power Generation | Turbine control systems with low-level DC inputs |
| Marine & Offshore | Marine control systems requiring intrinsic safety certification |
| Model | Channels | Working Voltage | Resistance | Current | Polarity | Primary Application |
|---|---|---|---|---|---|---|
| MTL7767+ | 2 | 12V | 100 Ω | 150mA | Positive (+) | 12V DC positive systems |
| MTL7764+ | 2 | 12V | 1,000Ω | 12mA | Positive (+) | Strain-gauge bridges |
| MTL7722+ | 2 | 18V | -- | -- | Positive (+) | 18V DC systems |
| MTL7706+ | 1 | 28V | 300Ω | 93mA | Positive (+) | General purpose positive polarity |
| Parameter | Detail |
|---|---|
| Mounting | Standard 35 mm T-section DIN rail (EN 60715) |
| Terminals | Removable screw terminals |
| Grounding | High-integrity earth connection made simultaneously when clipping onto DIN rail |
| Wire Entry | Angled to assist wiring in limited space enclosures |
| Clearance | Minimal — 12 mm width enables high-density installation |
| Operating Position | Any orientation |