Product Details:
Contact Now
Chat Now
|
| Condition: | Original Brand New | Warranty: | One Year |
|---|---|---|---|
| Application: | Oil Gas Chemical Industry | Shipping Way: | DHL FedEx |
| Highlight: | Eaton MTL7700 Zener Barrier,MTL7755AC intrinsic safety barrier,Crouse-Hinds series Zener Barrier |
||
The MTL7755AC is a high-performance 2-channel shunt-diode safety barrier (Zener barrier) from Eaton's Crouse-Hinds series MTL7700 range, specifically engineered for 2-wire and 3-wire floating bridge RTD applications requiring intrinsic safety protection in hazardous areas.
This passive device limits the voltage and current that can reach a hazardous area under fault conditions, preventing ignition of flammable atmospheres. With a safety description of 3V, 10 Ω, 300mA, the MTL7755AC is the ideal solution for protecting Pt100, Pt500, and Pt1000 RTD sensors in Zone 0, 1, and 2 hazardous locations (gas groups IIC, IIB, IIA).
| Code Segment | Meaning |
|---|---|
| MTL | MTL Instruments Group (now Eaton) |
| 77 | MTL7700 series — Shunt-diode safety barriers |
| 55 | Specific barrier configuration for floating RTD applications |
| AC | Non-polarized, AC/DC compatible configuration |
The "AC" suffix indicates a non-polarized barrier suitable for both AC and DC circuits, distinguishing it from polarity-sensitive models. This model is specifically designed for 2-wire and 3-wire RTDs (floating bridge).
| Parameter | Value |
|---|---|
| Manufacturer | Eaton (Crouse-Hinds series MTL) |
| Series | MTL7700 Range |
| Product Model | MTL7755AC |
| Product Type | Zener Barrier (Shunt-Diode Safety Barrier) |
| Number of Channels | 2 (dual-channel) |
| Polarity | AC (non-polarized) |
| Parameter | Value |
|---|---|
| Safety Description | 3 V, 10 Ω, 300 mA |
| Rated Supply Voltage DC | 3 V DC |
| End-to-End Resistance | 10 Ω |
| Maximum Current | 300 mA |
| Fuse Rating | 250 mA |
| Maximum Safe Area Voltage | 250 V AC/DC |
| Typical Application | 2- or 3-wire RTD (floating bridge) |
| Parameter | Value |
|---|---|
| Gas Groups | IIC, IIB, IIA |
| Zones | Zone 0, 1, 2 |
| NEC Hazardous Rating | Class I, Division 2; Class I, Zone 2 |
| ATEX/IECEx Rating | II (1) GD [Ex ia] IIC |
| ATEX Certificate | BAS01 ATEX 7217 |
| Ingress Protection | IP20 |
| Parameter | Value |
|---|---|
| Width | 12 mm - 12.6 mm |
| Height | 87 mm - 90 mm |
| Depth/Length | 105 mm - 106 mm |
| Weight | 0.106 kg - 0.200 kg |
| Enclosure Material | Polycarbonate |
| Mounting | 35 mm T-section DIN rail (EN 60715) |
| Terminals | Removable screw terminals, colour-coded |
| Parameter | Value |
|---|---|
| Minimum Operating Temperature | -20°C |
| Maximum Operating Temperature | +60°C to +65°C |
| Degree of Protection | IP20 |
| Certification | Status | Certificate Number | Region |
|---|---|---|---|
| CCC Ex (China) | Current (to 2030-09-01) | 2020322316002401 | China |
| ATEX | Certified | BAS01 ATEX 7217 | Europe |
| IECEx | Certified | -- | International |
| UL | Certified | -- | USA |
| CSA | Certified | -- | North America |
| TIIS (Japan) | Expired (2024-07-02) | TC16450 | Japan |
TIIS certification expired July 2, 2024. CCC Ex certification is valid until September 1, 2030.
The MTL7755AC is a passive shunt-diode safety barrier that operates on the Zener barrier principle. It limits both voltage and current that can be delivered to a hazardous area circuit under fault conditions.
The MTL7755AC is specifically designed for floating RTD temperature measurement protection in hazardous area installations:
| Industry | Application |
|---|---|
| Oil & Gas | 2-wire and 3-wire Pt100 temperature measurement on offshore platforms and refineries |
| Chemical Processing | Reactor temperature monitoring with floating bridge RTDs in explosive atmospheres |
| Pharmaceutical | Sterile processing temperature measurement requiring Ex ia IIC certification |
| Power Generation | Turbine bearing temperature monitoring with 2- or 3-wire RTDs |
| Industrial Automation | Process temperature measurement in hazardous locations |
| Analyzer Systems | Used in ABB AK102 analyzer systems for temperature measurement |
| Parameter | Detail |
|---|---|
| Mounting | Standard 35 mm T-section DIN rail (EN 60715) |
| Terminals | Removable screw terminals, colour-coded (blue for hazardous area) |
| Grounding | High-integrity earth connection made simultaneously when clipping onto DIN rail |
| Wire Entry | Angled to assist wiring in limited space enclosures |
| Terminal Capacity | Accommodates conductors up to 2.5 mm² |
| Clearance | Minimal — 12.6 mm width enables high-density installation |
| Operating Position | Any orientation |
| Item | Details |
|---|---|
| Part Number | MTL7755AC |
| Brand | Eaton (Crouse-Hinds series MTL) |
| Product Family | MTL7700 Range — Zener Barriers |
| Tariff Code | 85364900 |
| Weight | 0.106 kg - 0.200 kg |
| Country of Origin | India |
| Condition | New, Original, Factory Sealed |
Contact Person: Vivian Chan
Tel: +86 13510341645
Overall Rating
Rating Snapshot
The following is the distribution of all ratingsAll Reviews