Home ProductsIntrinsic Safety Barrier

Pepperl+Fuchs KCD2-SCD-Ex1.ES SIL 3 Certified Safety Barrier with Bidirectional HART Communication and 650 Ω Load Capacity

Certification
China Shenzhen Hengyo Power Technology Co., Limited certification
China Shenzhen Hengyo Power Technology Co., Limited certification
I'm Online Chat Now

Pepperl+Fuchs KCD2-SCD-Ex1.ES SIL 3 Certified Safety Barrier with Bidirectional HART Communication and 650 Ω Load Capacity

Pepperl+Fuchs KCD2-SCD-Ex1.ES SIL 3 Certified Safety Barrier with Bidirectional HART Communication and 650 Ω Load Capacity
Pepperl+Fuchs KCD2-SCD-Ex1.ES SIL 3 Certified Safety Barrier with Bidirectional HART Communication and 650 Ω Load Capacity

Large Image :  Pepperl+Fuchs KCD2-SCD-Ex1.ES SIL 3 Certified Safety Barrier with Bidirectional HART Communication and 650 Ω Load Capacity

Product Details:
Place of Origin: Singapore
Brand Name: Pepperl Fuchs
Certification: CE SIL3 UL
Model Number: KCD2-SCD-Ex1.ES
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: negotiable
Packaging Details: Pepperl Fuchs original package
Delivery Time: In stock
Payment Terms: T/T,Western Union
Supply Ability: 500pcs/month
Contact Now Chat Now

Pepperl+Fuchs KCD2-SCD-Ex1.ES SIL 3 Certified Safety Barrier with Bidirectional HART Communication and 650 Ω Load Capacity

Description
Condition: P+F Original Brand New Warranty: One Year
Shipping Way: DHL FedEx Application: Used For Intrinsic Safety Applications
Highlight:

Pepperl Fuchs SMART Current Driver

,

1-channel isolated safety barrier

,

intrinsic safety barrier with warranty

Pepperl+Fuchs KCD2-SCD-Ex1.ES 24VDC Power Rail DIN Rail Mount Safety Barrier
Product Overview

The KCD2-SCD-Ex1.ES is a high-performance 1-channel isolated barrier from Pepperl+Fuchs' K-System, specifically engineered to drive SMART I/P converters, electrical valves, and positioners located in hazardous areas. This signal conditioner repeats the 4...20 mA input signal from a control system to field devices while providing complete galvanic isolation.

With a compact 12.5 mm width and 24 V DC power supply (via Power Rail or terminals), the KCD2-SCD-Ex1.ES supports bidirectional HART communication for intelligent field device configuration and diagnostics.

Certified for SIL 3 (highest level for signal conditioners) according to IEC/EN 61508 and approved for hazardous area installation with [Ex ia Ga] IIC, [Ex ia Da] IIIC, and [Ex ia Ma] I certifications, this device delivers reliable, safety-rated performance for demanding explosive atmosphere applications.

Model Number Decoding
Code Segment Meaning
KCD2 K-System, 2-channel housing width (12.5 mm)
SCD SMART Current Driver – analog output signal conditioner
Ex1 1-channel with intrinsic safety (Ex) certification
.ES Specific variant with enhanced specifications – SIL 3 rating

The ".ES" suffix denotes the enhanced safety version with SIL 3 certification, distinguishing it from standard models.

Key Features & Benefits
  • SIL 3 Certified – Highest Safety Rating: Safety Integrity Level 3 according to IEC/EN 61508 – suitable for the most demanding safety instrumented systems (SIS)
  • Intrinsic Safety Certification: Certified with [Ex ia Ga] IIC for Zone 0, 1, and 2 hazardous areas – gas groups IIC (hydrogen, acetylene), IIB, and IIA. Also certified for dust (IIIC) and mining (Ma) applications
  • High Load Drive Capability: Drives loads up to 650 Ω with ≥13 V at 20 mA, providing sufficient power for demanding positioners and long cable runs
  • Bidirectional HART Communication: Digital signals can be superimposed on analog values at the field side or control side and transferred bi-directionally – supports full HART configuration and diagnostics
  • Integrated Test Sockets: Built-in test sockets for HART communicator connection are integrated into the device terminals – no need for external connection boxes
  • Line Fault Detection (LFD): An open or short field circuit presents high impedance (>100 kΩ) or low impedance (<50 Ω) to the control side, allowing alarm conditions to be monitored by the control system
  • Fault Indication: Faults are signaled by LEDs and a separate collective error message output, simplifying troubleshooting
  • Compact 12.5 mm Width: Ultra-slim design (housing type A2) maximizes DIN rail density in crowded control cabinets
  • Wide Operating Temperature: Functions reliably from -40°C to +70°C, suitable for harsh industrial environments
  • DNV Marine Approved: Certified for marine and offshore applications – suitable for shipbuilding installations
Technical Specifications
General Specifications
Parameter Value
Manufacturer Pepperl+Fuchs SE
Product Type SMART Current Driver / Signal Conditioner
Model KCD2-SCD-Ex1.ES
Signal Type Analog output
Channels 1
Housing Width 12.5 mm (type A2)
Functional Safety
Parameter Value
Safety Integrity Level (SIL) SIL 3 acc. to IEC/EN 61508
Supply
Parameter Value
Connection Power Rail or terminals 9+, 10-
Rated Voltage 19 ... 30 V DC
Ripple ≤ 10 %
Rated Current ≤ 33 mA at 24 V
Power Dissipation ≤ 700 mW at 20 mA and 500 Ω load
Power Consumption ≤ 800 mW
Input (Control Side)
Parameter Value
Connection terminals 5-, 6+
Input Signal 4 ... 20 mA, limited to approx. 25 mA
Input Voltage open loop voltage of the control system < 30 V, in line fault mode < 60 V
Voltage Drop approx. 6 V at 20 mA
Input Resistance > 100 kΩ, with field wiring open or < 50 Ω
Output (Field Side)
Parameter Value
Connection terminals 1+, 2-
Voltage ≥ 13 V at 20 mA
Current 4 ... 20 mA
Load 100 ... 650 Ω
Ripple 20 mV rms
Line Fault Detection field wiring open or < 50 Ω and test current < 2 mA
Applications

The KCD2-SCD-Ex1.ES is specifically designed for analog output and SMART field device driving in hazardous area installations:

Industry Application
Oil & Gas Driving I/P converters for pneumatic valve positioning on offshore platforms, refineries, and pipelines in Zone 0/1 areas
Chemical Processing Controlling SMART valve positioners and electrical actuators in explosive atmospheres
Pharmaceutical SIL 3 certified current driver for safety-related batch control with solvent handling equipment
Power Generation Driving turbine governor valves, boiler feedwater control valves with Ex ia protection
Mining Certified [Ex ia Ma] I for underground mining equipment requiring intrinsic safety
Marine & Offshore DNV-approved for shipbuilding – marine control systems with hazardous area valve actuation
Typical Field Devices Connected
  • SMART I/P (current-to-pressure) converters
  • SMART valve positioners with HART communication
  • Electrical actuators in hazardous areas
  • Solenoid valves in explosive atmospheres
Compliance & Certifications
Certification Status Details
SIL 3 Certified IEC/EN 61508 – Highest rating for signal conditioners
ATEX (Ex ia) Certified CESI 20 ATEX 016 X – II (1)G [Ex ia Ga] IIC
ATEX (Ex ec) Certified CESI 20 ATEX 017 X – II 3G Ex ec IIC T4 Gc
IECEx Certified IECEx CES 20.0009X – [Ex ia Ga] IIC, Ex ec IIC T4 Gc
DNV Marine Approved TAA00001WX – Marine and offshore applications
UL/cULus Listed E106378, Control Drawing 116-0471
CE Compliant EMC Directive 2014/30/EU
NAMUR Compliant NE 21:2017
RoHS Compliant Lead-free

Overall Rating

5.0
Based on 50 reviews for this supplier

Rating Snapshot

The following is the distribution of all ratings
5 stars
100%
4 stars
0%
3 stars
0%
2 stars
0%
1 stars
0%

All Reviews

S
Soh
Singapore Dec 19.2019
The goods arrive very fast, so down time was shorten. Ms Michelle was very helpful in answering all my questions and concerns. She is also very efficient in getting back to me with all the answers I needed. Overall 5 STARS.
B
Buntoro
Singapore Nov 4.2019
fast respond and delivery
M
Mahammad
Qatar Oct 14.2019
Appreciated your service & Support
Contact Details
Shenzhen Hengyo Power Technology Co., Limited

Contact Person: Vivian Chan

Tel: +86 13510341645

Send your inquiry directly to us (0 / 3000)