P+F Universal Temperature Converter KFD2-UT2-1
1-channel signal conditioner
24 V DC supply (Power Rail)
Thermocouple, RTD, potentiometer or voltage input
Current output 0/4 mA ... 20 mA
Sink or source mode
Configurable by PACTware
Line fault (LFD) and sensor burnout detection
Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511
Function
This signal conditioner provides the galvanic isolation between field circuits and control circuits.
The device converts the signal of a resistance thermometer, thermocouple, or potentiometer to a proportional output current. The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples. A fault is signalized by LEDs and a separate collective error message output.
The device is easily configured by the use of the PACTware configuration software. For additional information