Home ProductsPhoenix Contact Power Supply

MACX MCR-EX-SL-RPSSI-I-SP Phoenix Contact Repeater Power Supply 2924016

Certification
china Shenzhen Hengyo Power Technology Co., Limited certification
china Shenzhen Hengyo Power Technology Co., Limited certification
I'm Online Chat Now

MACX MCR-EX-SL-RPSSI-I-SP Phoenix Contact Repeater Power Supply 2924016

MACX MCR-EX-SL-RPSSI-I-SP Phoenix Contact Repeater Power Supply 2924016
MACX MCR-EX-SL-RPSSI-I-SP Phoenix Contact Repeater Power Supply 2924016 MACX MCR-EX-SL-RPSSI-I-SP Phoenix Contact Repeater Power Supply 2924016

Large Image :  MACX MCR-EX-SL-RPSSI-I-SP Phoenix Contact Repeater Power Supply 2924016

Product Details:
Place of Origin: Thailand
Brand Name: Phoenix Contact
Model Number: MACX MCR-EX-SL-RPSSI-I-SP
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: negotiable
Packaging Details: original package
Delivery Time: In stock
Payment Terms: T/T
Supply Ability: 500pcs/month
Contact Now Chat Now

MACX MCR-EX-SL-RPSSI-I-SP Phoenix Contact Repeater Power Supply 2924016

Description
Condition: Original Brand New Warranty: One Year
Shipping Way: DHL FedEx Application: Automation Industry
Highlight:

Phoenix Contact repeater power supply

,

MACX MCR power supply with warranty

,

Phoenix Contact industrial power supply

Ex i repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20 mA signals from the Ex area to a load (active or passive) in the safe area. 3-way electrical isolation, SIL 2 in accordance with IEC 61508, with Push-in connection

Signal: Repeater power supply operation
Description of the input Active current input, intrinsically safe
Number of inputs 1
Input signal Current
Current input signal 4 mA ... 20 mA
Current limitation 25 mA
Transmitter supply voltage > 16 V (20 mA)
> 15.3 V (22.5 mA)
Polarization and surge protection Yes
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Description of the input Passive current input, intrinsically safe
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop < 3.5 V (in input isolating amplifier operation)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)

Signal: Repeater power supply operation
Output description Current output (active and passive)
Number of outputs 1
Current output signal 4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Output description Current output (active and passive)
Current output signal 0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)

Overall Rating

5.0
Based on 50 reviews for this supplier

Rating Snapshot

The following is the distribution of all ratings
5 stars
0%
4 stars
0%
3 stars
0%
2 stars
0%
1 stars
0%

All Reviews

P
PressureTrol Honeywell L404F1102 Pressure Monitoring Controllers
Panama Jun 4.2024
Se los recomiendo
M
MTL5532 MTL Safety Barrier Eaton Crouse-Hinds series MTL5500 Pulse Isolator
Indonesia Nov 30.2023
After plugged, it plays well
M
M*r
Italy Mar 21.2020
Thankyou for your service and supply. I solved my problem on my broked machinery.
Contact Details
Shenzhen Hengyo Power Technology Co., Limited

Contact Person: Vivian Chan

Tel: +86 13510341645

Send your inquiry directly to us (0 / 3000)